3. Information ‘E’ codes
MULTICAL
®
601 continuously monitors a range of important functions. In case of
serious damage in the measuring system or installation, an ‘Info’ note appears on the
display. The information code can be read by pressing and holding the left top button,
until the ‘Info’ note shows up on the display. The information code only appears if
there is an error.
Information Time of
Code Description response
000 No error -
001 Supply voltage disconnected -
008 T1 temperature sensor out of the measuring range 1 to 10 min.
004 T2 temperature sensor out of the measuring range 1 to 10 min.
032 T3 temperature sensor out of the measuring range 1 to 10 min.
064 Cold water system leak 24 hrs
256 Heating system leak 24 hrs
512 Heating system crack Ca 120 sec
4. Assembly of the flow section
Before the assembly of the flow section, carefully wash the system and remove
protective lids (plastic diaphragms). The correct flow meter position (in supply and
return piping) is shown on the label of the MULTICAL
®
601 front. The direction of the
flow is marked with an arrow on the side of the flow meter.
Pipe union and sealing must be mounted as given in the picture. ULTRAFLOW
®
does
not require any direct sections in front of and behind the meter; however, to reach the
optimal installation conditions, we recommend the following:
Dimensions Recommendation
DN15 to DN80 qp 0.6 to qp 40 Min. 5 x DN in front of the meter
DN100 to DN250
qp 60 to qp 1000
Min. 10 x DN in front of the meter
Min. 3 x DN in front of the meter
CEN CR 13582 installation requirements must be followed.